Switchgear HB-12 Environmental Gas-Insulated Ring Main Unit "HB-12 Environmental Gas-Insulated Ring Main Unit" is an innovative and environmentally friendly metal-enclosed switchgear. It utilizes eco-friendly gases such as dry air or nitrogen for insulation, resulting in minimal or no greenhouse gas emissions. With a material recyclability rate exceeding 90% after the product's lifecycle, it minimizes environmental impact. The insulation components, except for the casing, primarily avoid the use of epoxy resin materials that are difficult to degrade, truly achieving green and sustainable objectives. Both the circuit breaker and load switch in this unit employ vacuum arc extinction technology, offering strong environmental adaptability, compact size, space-saving design, no need for SF6 gas detection and protection, reliable and safe operation, maintenance-free features, and intelligent capabilities. It represents the future direction of development for ring main units.It is designed for use in a 12kV, three-phase AC, 50Hz system with a single busbar or segmented busbar configuration. It serves as a complete distribution device for industrial and civil cable ring networks and distribution terminal projects. The unit is employed for the reception and distribution of electrical energy in urban residential distribution, small-scale secondary substations, switching stations, cable branch boxes, compact substations, industrial and mining enterprises, shopping malls, airports, subways, wind power generation, hospitals, sports stadiums, railways, tunnels, and other locations.
Parameter
Product Introduction
Technical Parameters

Operating Environment Requirements

● Air temperature: Maximum temperature 45°C, minimum temperature -25°C. 24-hour average temperature not exceeding 35°C.

● Relative humidity: Daily average relative humidity: ≤95%.

● Altitude ≤ 1500m

● Seismic Intensity: Not exceed 8 degrees.

● The surrounding air should not be significantly polluted by corrosive or combustible gases, water vapor, etc.

● No severe vibration.

● When used beyond the normal conditions specified in GB3906, it should be negotiated between the user and the manufacturer.

 

Standard

● GB/T 11022-2020

● GB/T 3906-2020

● GB/T 1985-2023

● GB/T 3804-2017

● GB/T 1984-2014

● GB/T 4208-2017

● GB/T 7354-2018

● GB/T 311.1-2012

 

Parameters Name

Unit

C Module

F Module

V Module

Load Switch

Combination Appliance

Vacuum Switch

Isolating / Grounding Switch

Rated Voltage

kV

123

Power Frequency Withstand VoltagePhase-to-phase / Across contact

Hz

42/48

Lightning Impulse Withstand VoltagePhase-to-phase / Across contact

kV

75/85

Rated Current

A

630

125

630

630

Breaking Capacity

Rated Closed-Loop Breaking Current

A

630

     

Rated Cable Charging Breaking Current

A

135

     

5% Rated Active Load Breaking Current

kA

31.5

     

Ground Fault Interruption Current

kA

20

     

Short-Circuit Breaking Current

kA

 

31.5

25

 

Rated Transfer Current

A

 

1500

   

Maximum Current for Fuse Accommodation

   

125

   

Rated Short-Circuit Closing Current

kA

63

80

25

 

Rated Short-Time Withstand Current

kA

25

 

25

25

Rated Short Circuit Duration

S

4

 

4

4

Component Life

Number of Times

5000

5000

10000

3000

Gas Pressure

kPa

0.025(20℃)

Annual Gas Leakage Rate

/

≤ 0.05%

Arc Extinction Method

/

Vacuum Arc Extinction

Protection LevelEnclosure/Casing

/

IP67/3X