Operating Environment Requirements
● Air temperature: Maximum temperature 45°C, minimum temperature -25°C. 24-hour average temperature not exceeding 35°C.
● Relative humidity: Daily average relative humidity: ≤95%.
● Altitude ≤ 1500m
● Seismic Intensity: Not exceed 8 degrees.
● The surrounding air should not be significantly polluted by corrosive or combustible gases, water vapor, etc.
● No severe vibration.
● When used beyond the normal conditions specified in GB3906, it should be negotiated between the user and the manufacturer.
Standard
● GB/T 11022-2020
● GB/T 3906-2020
● GB/T 1985-2023
● GB/T 3804-2017
● GB/T 1984-2014
● GB/T 4208-2017
● GB/T 7354-2018
● GB/T 311.1-2012
|
Parameters Name |
Unit |
C Module |
F Module |
V Module |
|
|
Load Switch |
Combination Appliance |
Vacuum Switch |
Isolating / Grounding Switch |
||
|
Rated Voltage |
kV |
123 |
|||
|
Power Frequency Withstand Voltage(Phase-to-phase / Across contact) |
Hz |
42/48 |
|||
|
Lightning Impulse Withstand Voltage(Phase-to-phase / Across contact) |
kV |
75/85 |
|||
|
Rated Current |
A |
630 |
125 |
630 |
630 |
|
Breaking Capacity |
|||||
|
Rated Closed-Loop Breaking Current |
A |
630 |
|||
|
Rated Cable Charging Breaking Current |
A |
135 |
|||
|
5% Rated Active Load Breaking Current |
kA |
31.5 |
|||
|
Ground Fault Interruption Current |
kA |
20 |
|||
|
Short-Circuit Breaking Current |
kA |
31.5 |
25 |
||
|
Rated Transfer Current |
A |
1500 |
|||
|
Maximum Current for Fuse Accommodation |
125 |
||||
|
Rated Short-Circuit Closing Current |
kA |
63 |
80 |
25 |
|
|
Rated Short-Time Withstand Current |
kA |
25 |
25 |
25 |
|
|
Rated Short Circuit Duration |
S |
4 |
4 |
4 |
|
|
Component Life |
Number of Times |
5000 |
5000 |
10000 |
3000 |
|
Gas Pressure |
kPa |
0.025(20℃) |
|||
|
Annual Gas Leakage Rate |
/ |
≤ 0.05% |
|||
|
Arc Extinction Method |
/ |
Vacuum Arc Extinction |
|||
|
Protection Level(Enclosure/Casing) |
/ |
IP67/3X |
|||