Manufacturing Standard
● IEC62271-1
● IEC62271-200
● GB/T 3906-2020
● GB/T 11022-2020
● GB/T 1984-2014
● GB/T 1985-2023
● GB/T 3804-2017
● DL/T 404-2018
● DL/T 593-2016
● Q/GDW 730-201212kV
Operating Environment Requirements
● Air temperature: Maximum temperature 45°C, minimum temperature -25°C. 24-hour average temperature not exceeding 35°C.
● Relative humidity: Daily average relative humidity: ≤95%.
● Altitude ≤ 1500m
● Seismic Intensity: Not exceed 8 degrees.
● Live Sealing Body and Fuse Barrel:IP67
● Switchgear Enclosure:IP4X
● The surrounding air should not be significantly polluted by corrosive or combustible gases, water vapor, etc.
|
Parameters Name |
Unit |
Content |
|
|
Rated Voltage |
kV |
12 |
|
|
Rated Current |
A |
630 |
1250 |
|
Rated Frequency |
Hz |
50 |
|
|
Power Frequency Withstand Voltage(Phase-to-phase / Across contact / Phase-to-ground) |
kV |
42/48/42 |
|
|
Lightning Impulse Withstand Voltage(Phase-to-phase / Across contact /Phase-to-ground) |
kV |
42/48/42 |
|
|
Rated Short-Time Breaking Current |
A |
25 |
31.5 |
|
Rated Short-Time Withstand Current |
kA |
25 |
31.5 |
|
Rated Peak Withstand Current |
kA |
63 |
80 |
|
Rated Peak Withstand Current |
kA |
63 |
80 |