Structural Features
● The cabinet structure is assembled, and the circuit breaker adopts a grounded handcart structure.
● Equipped with a brand new type of composite insulation vacuum circuit breaker, featuring good interchangeability and can be easily replaced.
● The handcart frame is equipped with a screw and nut propulsion mechanism, allowing easy movement of the handcart and preventing accidental damage to the propulsion structure
● All operations can be performed with the cabinet door closed. The interlocking between the main switch, handcart, and switchgear door adopts a mandatory mechanical interlock method to meet the "five prevention" function.
● The cable compartment has ample space and can accommodate the connection of multiple cables.
● The fast grounding switch is used for grounding and circuit short-circuit.
● The enclosure protection level is IP4X, and with the door open, the protection level is IP2X.
Operating Environment Requirements
● Ambient Temperature: Maximum +40°C, with a 24-hour average not exceeding +35°C, and minimum -15°C.
● Altitude: Altitude does not exceed 1000 meters.
● Relative Humidity: Daily average not exceeding 95%, monthly average not exceeding 90%.
● Seismic Intensity: Up to 8 degrees.
● Water Vapor Pressure: Daily average not exceeding 2.2kPa, monthly average not exceeding 90%.
|
Parameters Name |
Unit |
Content |
|
Rated Voltage |
kV |
40.5 |
|
Rated Current |
A |
1250/1600/2000 |
|
Rated Frequency |
Hz |
50 |
|
Rated Short-Time Withstand Current |
kA |
20/25/31.5 |
|
Rated Peak Withstand Current |
kA |
50/63/80 |
|
Rated Power Frequency Withstand Voltage |
kV |
95/1 min |
|
Rated Lightning Impulse Withstand Voltage |
kV |
185 |
|
Rated Short Circuit Duration |
s |
4 |
|
Protection Level |
/ |
IP2X |